ElevatorAtlas

High Density Housing / Commercial - Addition / Alteration - Elevator modernization Interior alterations to provide elevator modernization to the existing addressable two-stage fire alarm system to incorporate emergency recall of two elevators to meet the requirements of CSA-B44 in this existing 5-storey community care facility building. Scope of work: - Install three relay contacts in the machine room for recall signals to the elevator controller. - Install LEDs on the existing graphic annunciator to show new elevator recall smoke detector zones. - Reprogram existing addressable two-stage fire alarm control panel to suite the automatic emergency elevator recall function. - Install new receptacles, light switches and new feeder cables, elevator controllers, operating fixtures, and reprogram existing addressable FAS initiation devices to allow for activation of the automatic emergency elevator recall sequence. ******THIS PERMIT HAS BEEN REVIEWED AND ISSUED UNDER THE REQUIREMENTS OF VBBL 2019 ******** Building Review Branch Notes: 1. Arch. B & Elec. B submitted by B. W. Town, P. Eng. 2. Automatic emergency recall (main - ground floor, alternate - 2nd floor) 3. Assurance letter from Professional confirming alterations do not require variance or impact to the existing equivalencies (AL401258) is submitted.

1880 RENFREW STREET, Vancouver, BC V5M 3H9 · Vancouver, BC

1